Welcome To TUNKIA !      Electrical Measurement    Magnetic Measurement
You are here: Home » Products » Industrial Instrument Testing » TD6600 Relay Protection Tester Verification Device » TD6600 Relay Protection Tester Calibration Device

loading

Share to:
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
sharethis sharing button

TD6600 Relay Protection Tester Calibration Device

TD6600 is an intelligent instrument dedicated to testing the technical performance of relay protection testers. The instrument can accurately measure multiple channels of AC/DC voltages, currents, and small signal voltages. Its accuracy is Class 0.02. The user can complete the full-function test of the relay protection tester of Class 0.05 and below with this instrument. Compared with traditional methods, this instrument has the characteristics of simple connection and convenient operation.
Availability:
Quantity:
  • TD6600

  • TUNKIA

TD6600 Relay Protection Tester Verification Device

TD6600 Relay Protection Tester Verification Device 

1. Summary

TD6600 is an intelligent instrument dedicated to testing the technical performance of relay protection testers. The instrument can accurately measure multiple channels of AC/DC voltages, currents, and small signal voltages. Its accuracy is Class 0.02. The user can complete the full-function test of the relay protection tester of Class 0.05 and below with this instrument. Compared with traditional methods, this instrument has the characteristics of simple connection and convenient operation.

2. Features

  • 6-channel of AC/DC Voltage Measurement200 mV1100 V

  • 6-channel of AC/DC Current Measurement1 mA60 A

  • 12-channel of Small Signal Measurement1 mV7.7 V

  • Frequency10 Hz1 kHz

  • Phase0.000°359.999°

  • Voltage/Current AccuracyClass 0.02

  • Harmonic/Ripple Measurement Function

  • 4 Pairs of Binary Input, 4 Pairs of Binary Output

  • Time Measurement Function


3. Application


TUNKIA TD6600 Relay Protection Tester Calibration Device



4. Instrument Appearance

Instrument Front/Side Panel

TUNKIA TD6600 Relay Protection Tester Calibration Device

Number

Function

The feet can be folded to raise the instrument slightly to a certain angle to obtain the best viewing angle for operation and reading.

The instrument handle is convenient for carrying the instrument.

LCD touch color screen, intuitive display of multiple power levels, full touch operation, greatly improving the usability of the instrument.

6-channel current input terminal.

6-channel current input terminal.


Instrument Rear Panel

TUNKIA TD6600 Relay Protection Tester Calibration Device

Number

Function

8-channel switch output terminals, including 4-channel optocoupler outputs and 4-channel empty contact outputs.

4-channel switch input terminals.

12-channel small signal measurement terminals.

USB interface, RS232 interface, LAN interface, used to connect to the computer for communication.

220V power input socket with ship type switch and fuse.


5. Characteristics

Wide Measuring Range

TUNKIA TD6600 Relay Protection Tester Calibration Device

A wide range of measurements can meet the calibration of relay protection testers commonly used in power systems

Fully automatic range switching, built-in protection module in the circuit, and alarm prompt when necessary.


Ripple Measurement Function

TUNKIA TD6600 Relay Protection Tester Calibration Device

In the DC measurement mode,

TD6600 can analyze the ripple from 1 Hz to 5 kHz, measure its effective value, and complete the ripple test of DC voltage/current.


Harmonic Measurement Function and Graphical Display

TUNKIA TD6600 Relay Protection Tester Calibration Device

Number

Function

The instrument can measure 2nd to 63rd harmonics, and observe the waveforms of the electric quantities of each phase after the harmonics are loaded.

The histogram visually displays the frequency spectrum of each harmonic (fundamental wave is 100%).

It displays the content and phase value of the 2nd to 63rd harmonic.

It can visually display the phasor diagram, the output voltage and current amplitude and phase direction of each channel.

Display the waveform of the measured power in real time, and intuitively analyze the waveform distortion of the measured power.


Binary Input/Output and Time Measurement

TUNKIA TD6600 Relay Protection Tester Calibration Device

Number

Function

Built-in time measurement module, response time uncertainty up to 2 μs, can complete response time and synchronization test.

Binary Input4 pairs, open contact or TTL level (0~5) V.

Binary Output4 pairs of optocoupler output, 4 pairs of open contact output.

Binary Output4 pairs of open contact outputs.


TD6610 With Load Capacity Test (option)

TUNKIA TD6600 Relay Protection Tester Calibration Device

TD6610 is a program-controlled and adjustable electronic load, which is specially used to test the load capacity of voltage source and current source.

Voltage source electronic loads up to 100 VA, current source electronic loads up to 240 W.

The load power factor is adjustable and meet the requirements of the load capacity test with an adjustable range of 0.4L ~ 1.0 ~ 0.4C.


Communication Interface and Special Software

TUNKIA TD6600 Relay Protection Tester Calibration Device

The rear panel of the instrument is equipped with rich communication interfaces such as RS232, USB, LAN, etc., which is convenient for building a fully automatic test system。

Equipped with special test software, and automatically generate test reports to improve test efficiency.


6. Specifications

6.1 AC/DC Measurement (6-channels for voltage/current)

Range

Resolution

Uncertainty (k=2)

( ppm*RD+ppm*RG)[1]

Temperature Coefficient

ppm*RD /℃ @ ( 1530 ) ℃

2 V

10 μV

120 + 80

<5

5 V

10 μV

120 + 80

< 5

10 V

0.1 mV

120 + 80

< 5

20 V

0.1 mV

120 + 80

< 5

50 V

0.1 mV

120 + 80

< 5

100 V

1 mV

120 + 80

< 5

200 V

1 mV

120 + 80

< 5

500 V

1 mV

120 + 80

< 5

1000 V

10 mV

120 + 80

< 5

Note1】: RD is the reading value, RG is the range value, the same below.

 

Range

Resolution

Uncertainty (k=2)

( ppm*RD+ppm*RG)[1]

Temperature Coefficient

ppm*RD /℃ @ ( 1530 ) ℃

10 mA

0.1 μA

120 + 80

< 5

20 mA

0.1 μA

120 + 80

< 5

50 mA

0.1 μA

120 + 80

< 5

100 mA

1 μA

120 + 80

< 5

200 mA

1 μA

120 + 80

< 5

500 mA

1 μA

120 + 80

< 5

1 A

10 μA

120 + 80

< 5

2 A

10 μA

120 + 80

< 5

5 A

10 μA

120 + 80

< 5

10 A

0.1 mA

120 + 80

< 5

20 A

0.1 mA

120 + 80

< 5

50 A

0.1 mA

120 + 80

< 5

lVoltage measurement range: 200mV1100 V, current measurement range: 1 mA60 A, manual/automatic shift.

6.2 AC/DC small signal voltage measurement (12-channel)

Range

Resolution

Uncertainty (k=2)

( ppm*RD+ppm*RG)[1]

Temperature Coefficient

ppm*RD /℃ @ ( 1530 ) ℃

10 mV

0.1 μV

120 + 10

10

20 mV

0.1 μV

120 + 10

10

50 mV

0.1 μV

120 + 10

10

100 mV

1 μV

120 + 10

10

200 mV

1 μV

120 + 20

10

500 mV

1 μV

120 + 40

10

1 V

10 μV

120 + 80

10

2 V

10 μV

120 + 160

10

5 V

10 μV

120 + 400

10

lMeasurement range: 1 mV7.7 V, 6-digit display, manual/automatic shift

 

6.3 Frequency Measurement

Voltage Frequency

Resolution

Uncertainty (k=2)

( ppm*RD+ppm*RG)

10Hz≤F≤65Hz

0.0001 Hz

0.0003 Hz

65Hz<F≤100Hz

0.0001 Hz

0.001 Hz

100Hz<F≤450Hz

0.001 Hz

0.003 Hz

450Hz<F≤1 kHz

0.001 Hz

0.005 Hz

 

6.4 Phase/Ripple/Harmonic Measurements

lPhase: The frequency of the input voltage and current are both 40 Hz70 Hz

Measuring range0.000°359.999°Uncertainty (k=2)0.02°

lHarmonic measurement: 2nd to 63rdUncertainty (k=2)0.02%*RG

lRipple measurement (frequency band)1 Hz5 kHzUncertainty (k=2)0.05%*RG , Effective value display.


6.5 AC Power Measurement

Type

Range

Uncertainty (k=2)

Active Power

Combination of AC voltage and AC current

@40 Hz70 Hz

0.05%

Reactive Power

0.1%

Apparent Power

0.1%

Power Factor

-1.000...0.000...1.000

0.05%

 

6.6 Switching Value and Time Measurement

lBinary Input: Open contacts or TTL level (0~5) V, 4 pairs, response time: 20 µs

lBinary Output: Optocoupler output, 4 pairs, contact capacity: 40 V/30 mA, response time: 20 µs

lOpen contact output, 4 pairs, contact capacity: 220 V/0.5 A

lResponse time measurement uncertainty/ Synchronization measurement uncertainty (k=2): 2 μs

lClosing angle measurement uncertainty (k=2)0.1°


7. General Specifications

Power Supply

AC ( 220 ± 22 ) V( 50 ± 2 ) Hz

Warm-up Time

20 minute

Maximum Power

100 VA

Temperature Performance

Working Temperature0°C~45°C

Storage Temperature-20°C~70°C

Humidity Performance

Working Humidity< 80% @ 30°C< 70% @ 40°C< 40% @ 50°C

Storage Humidity(20%~80%) R·Hno condensation

Altitude

< 3000 m

Weight

About 18 kg

Communication Interface

RS232USBLAN

Dimensions

480 mm(W) × 400 mm(D) × 270 mm(H) (excluding handles and feet)

TUNKIA TD6600 Relay Protection Tester Calibration Device


8. Accessories List

Number

Picture

Name

Specification

Quantity

Note

1

TUNKIA TD6600 Relay Protection Tester Calibration Device

Voltage Test Leads

1.5m / 2.1mm2 / Φ4-Φ4 socket

Green: 4 Yellow: 4

Red: 16

Black: 20

Standard Accessories

2

TUNKIA TD6600 Relay Protection Tester Calibration Device

Current Test Leads

1.5m / 8mm2 / Φ4-Φ4

socket

Green: 2 Yellow: 2

Red: 2

Black: 6

Standard Accessories

3

U-shaped Insert

Φ12 thin insert /Φ4 jack

Red: 6

Black: 6

Standard Accessories

4

TUNKIA TD6600 Relay Protection Tester Calibration Device

Small Signal Test Leads

1.5m/6-core aviation head/3 sets of alligator clips

4

Standard Accessories

5

TUNKIA TD6600 Relay Protection Tester Calibration Device

Network Cable

——

1

Standard Accessories

6

TUNKIA TD6600 Relay Protection Tester Calibration Device

Universal Serial Cable

USB to RS232

1

Standard Accessories

7

TUNKIA TD6600 Relay Protection Tester Calibration Device

Power Cable

AC 220V10A

1

Standard Accessories

8

TUNKIA TD6600 Relay Protection Tester Calibration Device

Glass Fuse

F4A250V

3

Standard Accessories

9

TUNKIA TD6600 Relay Protection Tester Calibration Device

Packaging Box

Aluminum Alloy Box

1

Standard Accessories



Number

Picture

Name

Specification

Quantity

Note

1

TUNKIA TD6600 Relay Protection Tester Calibration Device

TD6610

Electronic Load

Voltage source electronic load up to 100 VA;

Current source electronic load up to 240 W;

The load power factor is adjustable in the range of 0.2L~1.0~0.2C.

1

Optional Accessories

2

TUNKIA TD6600 Relay Protection Tester Calibration Device

Special Test Software

Card U Disk

1

Optional Accessories

3

TUNKIA TD6600 Relay Protection Tester Calibration Device

Portable Case

——

1

Optional Accessories

Note: The above accessories need to be purchased separately and specified in the order contract.




Previous: 
Next: 

SIGN UP FOR NEWSLETTER

Get latest deals, newsletter and technical information

INFORMATION

CONTACT US

 WhatsApp:+86-18773180215
     Wechat: 18773180215
 Phone: +86-18773180215
 E-mail: global@tunkia.com
E-mail: Eugene@tunkia.com
 Address: NO.16 Panpan Road, Changsha
Copyright  2021 TUNKIA Co., Ltd. All Rights Reserved. Supported by leadong.comSitemap