1. Summary
TD2410 is a high precision and multi-function AC standard high voltage source with wide rang. It’s applied for calibrating AC high voltage meter, withstanding voltage testers, high voltage probe etc.
2. Features
• AC voltage output: 1kV~35 kV.
• Accuracy class: 0.02, 0.05.
• Frequency: 45 Hz~65 Hz.
• 2nd~11th harmonic output (option).
• Short-circuit and overload protection.
• LCD touch screen
• High voltage switch for safety.
• RS232 interface.
3. Application
☆ Calibration for AC HV meter or Probe |
|
• AC voltage ( ACV ) output: 1 kV~35 kV • Apply to the calibration of alternating high voltage meter,high voltage probe etc. |
4. Characteristics
☆ Security of Operation |
|
• High voltage output indicator which can warning high voltage danger • Optical grating (option): Optical grating is controlled by software,if someone passing through the optical grating TD2410 will cut off the output immediately for safety. |
☆ Multiple Output Mode |
|
• “Direct output”mode,User can set output value by touch screen. |
|
• Touch “Calibration point”of screen for “% setting”. |
☆ Harmonic Function | |
| |
S/N | Function description |
| It can output 2nd~11th harmonic, and set harmonic amplitude. |
| Users can select the harmonics and set up harmonic parameter |
| Harmonic interface for output. |
5. Specifications
Range | Resolution | Stability (%/min) | Accuracy ±(ppm of reading + ppm of range) [1] | Distortion ( % ) | |
Class 0.05 | Class 0.02 | ||||
10 kV | 100 mV | 0.01 | 300 + 200 | 120 + 80 | ≤ 0.5 |
35 kV | 100 mV | 0.01 | 300 + 200 | 120 + 80 | ≤ 0.5 |
Note [1] : (ppm = parts per million) (e.g.,10ppm = 0.001%). |
• Output range: 1 kV~35 kV,6 digits true RMS,max burden: 600 VA
• Frequency range: 45.000 Hz~65.000 Hz,uncertainty:0.01Hz
• Short-circuit and overload protection
• Harmonic function(option): 2nd~11th harmonic, 0~25% adjustable
6. General Specifications
Power Supply | AC (220 ± 22) V,(50 ± 2) Hz |
Temperature | Working temperature:0℃~45℃; Storage temperature:-20℃~70&℃ |
Humidity | Working humidity:< 80% @ 30℃,< 70% @ 40℃,< 40% @ 50&℃ Storage humidity:(20%~80%) R·H,non-condensing |
Interface | RS232 interface |
7. Ordering Information
Advanced Multifunction Calibrator Advanced Electrical Reference Standards Electric Vehicle (EV)Charging Facility Tester AC/DC Standard Source /Meter Single-phase/Three-phase Standard Meter Magnetic Parameters Measurement and Calibration Magnetic Material Testing Equipment Electrical Steel Testing Equipment