TD1600 Precision AC Calibrator

Availability:
Quantity:

Introduction

  • TD1600, a single-phase AC calibrator with wide range, high precision and multifunction.

  • The apparatus can output high accuracy AC voltage, current and power, and the optional accuracy are 0.05% and 0.02%. Applied to calibrate various AC electrical measuring instruments.


Features

  • AC Electrical Parameter Output: Voltage is up to 1100 V, current is up to 110 A.

  • Frequency and Phase Adjustment: Frequency: 45 Hz ~ 70 Hz.

  • AC Power Output: Measure the active power, reactive power, apparent power and power factor.

  • Value Output Mode: Standard source and output source modes, easy to calibrate both digital meters and analogue meters.

  • Value Adjustment Method: Fixed-point, rotary encoder, step and potentiometer (option).

  • Output Switch: The output can be turned on/off arbitrarily by one-touch operation.

  • Automatical Error Calculation: Set the measured values of the checked meter, and adjust the value output to automatically calculate the errors of the checked meter.

  • Excellent Human-computer Interaction: Large LCD touch screen display, touch and button operation modes, easy for users to measure manually.

  • Harmonic (Option): Load 2nd to 31st harmonics with variable amplitude and phase for impact test.

  • Proprietary Software (Option): Support the calibration of the checked meters by semi-automatic or full-automatic, data management and report export.

Specification


AC Voltage Output

Range

Stability   (%/min)

Accuracy   (k = 2)

(ppm*RD + ppm*RG)

Max. Load   Current

(mA)

0.05%

0.02%

0.05%

0.02%

1 V

0.01

0.005

300 + 200

120 + 80

500

3 V

0.01

0.005

300 + 200

120 + 80

500

10 V

0.01

0.005

300 + 200

120 + 80

500

30 V

0.01

0.005

300 + 200

120 + 80

500

60 V

0.01

0.005

300 + 200

120 + 80

800

100 V

0.01

0.005

300 + 200

120 + 80

500

150 V

0.01

0.005

300 + 200

120 + 80

400

200 V

0.01

0.005

300 + 200

120 + 80

250

300 V

0.01

0.005

300 + 200

120 + 80

150

400 V

0.01

0.005

300 + 200

120 + 80

100

600 V

0.01

0.005

300 + 200

120 + 80

80

750 V

0.01

0.005

300 + 200

120 + 80

60

1000 V

0.01

0.005

300 + 200

120 + 80

50


AC Current Output

Range

Stability   (%/min)

Accuracy   (k = 2)

(ppm*RD +   ppm*RG)

Max. Inductive

Load (V)

0.05%

0.02%

0.05%

0.02%

1 mA

1 μA

0.5 μA

300 + 2 μA

120 + 1 μA

120

2 mA

1 μA

0.5 μA

300 + 2 μA

120 + 1 μA

120

5 mA

1 μA

0.5 μA

300 + 2 μA

120 + 1 μA

120

10 mA

0.01

0.005

300 + 200

120 + 80

120

20 mA

0.01

0.005

300 + 200

120 + 80

120

50 mA

0.01

0.005

300 + 200

120 + 80

120

100 mA

0.01

0.005

300 + 200

120 + 80

120

200 mA

0.01

0.005

300 + 200

120 + 80

120

500 mA

0.01

0.005

300 + 200

120 + 80

100

1 A

0.01

0.005

300 + 200

120 + 80

50

2 A

0.01

0.005

300 + 200

120 + 80

25

5 A

0.01

0.005

300 + 200

120 + 80

10

10 A

0.01

0.005

300 + 200

120 + 80

5

20 A

0.01

0.005

300 + 200

120 + 80

2.5

30 A

0.01

0.005

300 + 200

120 + 80

2.5

50 A

0.01

0.005

300 + 200

120 + 80

1.5

100 A

0.01

0.005

300 + 200

120 + 80

0.8


Output Characteristics of Voltage and Current

  • Output Range of Voltage: 100 mV ~ 1100 V

  • Output Range of Current: 0.1 mA/ 20 mA ~ 110 A

  • Range Switching: Automatic or Manual.

  • Resolution: 0.001 %*RG; Display: 6 digits; Distortion: <0.2 %

  • 1 mA、2 mA、5 mA are small range option.


Frequency, Phase and Harmonic (Option)

Type

Range

Resolution

Accuracy

Frequency

45.000 Hz   ~ 70.000 Hz

0.001 Hz

0.005 Hz

Phase

0.0000 ° ~   359.9999 °

0.005 °

0.05 °

Type

Order

Amplitude

Variable   Phase

Harmonic

2nd   to 31st

0 ~ 25 %

0 ~ 359.9   °


Power Output

Type

Stability (%/min)

Accuracy   (k = 2) %*FS

0.05%

0.02%

0.05%

0.02%

Active Power

0.01

0.005

0.05

0.025

Reactive Power

0.02

0.01

0.1

0.05

Apparent Power

0.02

0.01

0.1

0.05

Power Factor

0.02

0.01

0.1

0.05

  • Output Range of AC Power: Combination of AC voltage range and AC current range.

  • Range of Power Factor: -1.0000…0.0000…+1.0000

  • Active Power (|cosφ| ≥0.5), Reactive Power (|sinφ| ≥0.5)

Previous: 
Next: 

SIGN UP FOR NEWSLETTER

Get latest deals, newsletter and technical information

INFORMATION

CONTACT US

 WhatsApp:+86-18773180215
     Wechat: 18773180215
 Phone: +86-18773180215
 E-mail: global@tunkia.com
E-mail: Eugene@tunkia.com
 Address: NO.16 Panpan Road, Changsha
Copyright  2021 TUNKIA Co., Ltd. All Rights Reserved. Supported by leadong.comSitemap